The UPS dashboard shows the following

  • UPS Model
  • UPS and Battery Status
  • Graphs for:
    • Load and Efficiency
    • Run Time Remaining
    • Voltage (both input and output)
    • Battery Charge Capacity
    • Time On Battery
    • Battery Temperature (Celcius)
    • Energy Usage (kWh)
    • Current (Ampere Load)

All graphs, where possible, use high precision counters.

Collector Configuration Details

  [[inputs.snmp.field]]
    name = "hostname"
    oid = "RFC1213-MIB::sysName.0"
    is_tag = true

  [[inputs.snmp.field]]
    name = "uptime"
    oid = "DISMAN-EXPRESSION-MIB::sysUpTimeInstance"

  [[inputs.snmp.field]]
    name = "model"
    oid = "PowerNet-MIB::upsBasicIdentModel.0"

  [[inputs.snmp.field]]
      name = "name"
      oid = "PowerNet-MIB::upsBasicIdentName.0"

  [[inputs.snmp.field]]
      name = "upsBasicBatteryTimeOnBattery"
      oid = "PowerNet-MIB::upsBasicBatteryTimeOnBattery.0"

  [[inputs.snmp.field]]
      name = "upsAdvBatteryRunTimeRemaining"
      oid = "PowerNet-MIB::upsAdvBatteryRunTimeRemaining.0"

  [[inputs.snmp.field]]
      name = "upsAdvBatteryReplaceIndicator"
      oid = "PowerNet-MIB::upsAdvBatteryReplaceIndicator.0"

  [[inputs.snmp.field]]
      name = "upsHighPrecBatteryCapacity"
      oid = "PowerNet-MIB::upsHighPrecBatteryCapacity.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsHighPrecBatteryTemperature"
      oid = "PowerNet-MIB::upsHighPrecBatteryTemperature.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsBasicOutputStatus"
      oid = "PowerNet-MIB::upsBasicOutputStatus.0"

  [[inputs.snmp.field]]
      name = "upsHighPrecOutputLoad"
      oid = "PowerNet-MIB::upsHighPrecOutputLoad.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsHighPrecOutputEfficiency"
      oid = "PowerNet-MIB::upsHighPrecOutputEfficiency.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsHighPrecOutputVoltage"
      oid = "PowerNet-MIB::upsHighPrecOutputVoltage.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsHighPrecInputLineVoltage"
      oid = "PowerNet-MIB::upsHighPrecInputLineVoltage.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsHighPrecOutputCurrent"
      oid = "PowerNet-MIB::upsHighPrecOutputCurrent.0"
      conversion = "float(1)"

  [[inputs.snmp.field]]
      name = "upsHighPrecOutputEnergyUsage"
      oid = "PowerNet-MIB::upsHighPrecOutputEnergyUsage.0"
      conversion = "float(1)"


  # IF-MIB::ifTable contains counters on input and output traffic as well as errors and discards.
  [[inputs.snmp.table]]
    name = "interface"
    inherit_tags = [ "hostname" ]
    oid = "IF-MIB::ifTable"

    # Interface tag - used to identify interface in metrics database
    [[inputs.snmp.table.field]]
      name = "ifDescr"
      oid = "IF-MIB::ifDescr"
      is_tag = true

  # IF-MIB::ifXTable contains newer High Capacity (HC) counters that do not overflow as fast for a few of the ifTable counters
  [[inputs.snmp.table]]
    name = "interface"
    inherit_tags = [ "hostname" ]
    oid = "IF-MIB::ifXTable"

    # Interface tag - used to identify interface in metrics database
    [[inputs.snmp.table.field]]
      name = "ifDescr"
      oid = "IF-MIB::ifDescr"
      is_tag = true

  # EtherLike-MIB::dot3StatsTable contains detailed ethernet-level information about what kind of errors have been logged on an interface (such as FCS error, frame too long, etc)
  [[inputs.snmp.table]]
    name = "interface"
    inherit_tags = [ "hostname" ]
    oid = "EtherLike-MIB::dot3StatsTable"

    # Interface tag - used to identify interface in metrics database
    [[inputs.snmp.table.field]]
      name = "ifDescr"
      oid = "IF-MIB::ifDescr"
      is_tag = true